Pad Foundation In Clay [Design Of Soil And Concrete]

Pad foundation in clay - Structural design of the soil capacity and concrete and reinforcement verification

Designing a pad foundation is never really taught fully in university or textbooks. πŸ™ˆπŸ™ˆ

It’s either the geotechnical or the reinforced concrete design.

But both are necessary for structural documentation. πŸ“„πŸ“„

That’s why in this post we’ll show you, step-by step, how to design a pad foundation in clay with a worked example. We’ll cover both the geotechnical verification of clay according to Eurocode EN 1997-1 and the reinforced concrete verification according to Eurocode EN 1992-1-1.

Not much more talk, let’s dive into it. πŸš€πŸš€

πŸ™‹β€β™€οΈ What Is A Pad Foundation?

Pad foundations serve as a support system for columns in buildings. Typically, they consist of a concrete “block”, and in most cases steel reinforcement to resist tensile forces. These foundations are placed on soil and spread the concentrated load from the column to a wider area of the soil.

Pad footings or foundations in general stand on sand, clay, rock, or a mix of 2 soil types. In this tutorial, we design a pad foundation which is embedded in clay. But we have already written an article about pad foundations in sand.

Pad foundations can have different shapes, from circular πŸ”΅πŸ”΅ to rectangular 🟦🟦 bases.

3D visualization of a rectangular pad foundation supporting a column.
3D visualization of a rectangular pad foundation supporting a column.

πŸ“ƒ Process of Pad Foundation Design

Before we dive into the nerdy calculations πŸ˜‹πŸ˜‹, it’s good to get an overview of the steps that need to be taken to design a pad foundation, which is supported by sand and exposed to a vertical load.

Pad foundation in clay exposed to point load.
  1. Calculate characteristic loads that act on pad foundation
  2. Load combinations
  3. Define properties of the sand and concrete
  4. Geotechnical design – bearing resistance verification of clay
  5. Reinforced concrete design – bending verification
  6. Reinforced concrete design – shear verification

⬇️ Characteristic Loads

The loads of a structure depend on its location, geometry, building type and other factors.

We’ll assume in this tutorial that we design the pad foundation of a multi-storey building. πŸ‘‡πŸ‘‡

Multi-storey building with pad foundations.

Now to calculate the characteristic loads acting on the pad foundation, we need to know what loads are applied where and how the loads travel through the different elements and to the foundations.

In this simplified design guide, the following vertical loads are considered:

Vertical loads applied to the building.
Vertical loads applied to the building.

Now, in the structural design of such a building, a lot more loads are considered such as seismic and wind load and imperfections.

But we’ll do a lot of assumptions in this tutorial. If you want to learn more about all the loads that act on a building, then check out this article.

Load transfer

❗ The following load transfer explanation works if the building is a traditional structure with simply supported beams and columns❗

  1. Live, snow and dead load (self-weight of roofing) are applied as area loads [kN/m2] on the roof. This could be precast hollow core slabs, which transfer the loads to beams.
  2. By multiplying the area loads (live, snow, dead load) with the spacing of the beams, line loads are calculated. These line load can now be applied to the beams.
  3. The reaction force of a beam is then the characteristic vertical load that is applied to the column which supports the beam.
  4. We do that for every floor, and the reaction forces are added up and applied to the pad foundation.
Characteristic loads that act on pad foundation.

The following characteristic load values are assumptions.

$g_{k}$380 kNCharacteristic value of dead load
$q_{k}$250 kNCharacteristic value of live load
$s_{k}$15 kNCharacteristic value of snow load

❗❗ The characteristic values of loads depend on a lot of different factors like location, National Annex and geometry of the building and roof to name just a few. Loads therefore need to be calculated for every structure. ❗❗

βž• Load combinations

Load combinations combine several load cases and multiply the characteristic loads with safety factors.

Check out our extensive article about load combinations to learn more about partial safety factors and how to set up the combinations.

ULS Load combinations

LC1$1.35 \cdot 380 kN $$513 kN$
LC2$1.35 \cdot 380 kN + 1.5 \cdot 250 kN$$888 kN$
LC3$1.35 \cdot 380 kN + 1.5 \cdot 250 kN + 0.6 \cdot 1.5 \cdot 15 kN$$901.5 kN$
LC4$1.35 \cdot 380 kN + 1.5 \cdot 15 kN$$535.5 kN$

You can also use our load combination generator, which creates the load combinations automatically for you, and you can copy & paste the table into Word. πŸ”₯πŸ”₯

Result from load combination generator.

So the vertical design load we are designing the pad foundation for is:

$$V_{d} = 901.5 kN$$

🟫 Geotechnical Soil Properties

The pad foundation is embedded into the soil. In our example, it’s clay.

For this tutorial, we use the following soil properties.

Density sand$\gamma_{clay} = 18 kN/m^3$
Undrained shear strength$c_u = 100 kN/m^2$
Partial factor (shear strength)
Depends on the country
$\gamma_{cu} = 1.8$
Design undrained shear strength$c_{ud} = \frac{c_u}{\gamma_{cu}} = 55.6 kN/m^2$
Density water$\gamma_w = 10 kN/m^3$
Density wet sand$\gamma ‘ = \gamma_{clay} – \gamma_w = 8 kN/m^3$

⬜ Concrete and Reinforcement Properties

For this tutorial, we use the following concrete and reinforcement properties.

Concrete compression strength$f_{c.k} = 25 MPa$
Concrete tensile strength$f_{ctm} = 2.6 MPa$
Partial factor – in-situ
Depends on the country
$\gamma_{c} = 1.45$
Design concrete compression strength$f_{c.d} = \frac{f_{c.k}}{\gamma_{c}} = 17.24 MPa$
Design concrete tensile strength$f_{c.t} = \frac{f_{ctm}}{\gamma_{c}} = 1.79 MPa$
Reinforcement yield strength$f_{y.k} = 550 MPa$
Density concrete$\gamma_c = 24 kN/m^3$
Concrete cover$c = 50 mm$
Partial factor – reinforcement
Depends on the country
$\gamma_{s} = 1.2$
$\epsilon_{cu3} = 0.35%$
$\epsilon_{c3} = 0.175%$
$\lambda = 0.8$
$\epsilon_{yd} = 0.208%$
$\eta = 1.0$

πŸ•΅οΈβ€β™‚οΈ Geometry Of The Foundation And Column

Geometry of the pad foundation.
Geometry of the pad foundation.
Width$w = 1.7 m$
Length$l = w = 1.7 m$
Height$h = 0.5 m$
Depth of embedded foundation$h’ = h = 0.5 m$
Width of column$w_c = 0.4 m$
Inclination of the foundation base to the horizontal$\alpha = 0$
Dead load of foundation (self-weight)$G_k = w \cdot l \cdot h \cdot \gamma_c = 34.7 kN$
New vertical design load$V_d = V_d + 1.35 \cdot G_k = 948.3 kN$

Now, in countries, where the temperatures can get low, it’s common to have a minimum depth, where frost can’t affect the groundwater any more. Because if it does, it can lift up the foundation.

In Denmark, for example, 0.9 m is a common minimum depth.

✍️ Geotechnical Design – Bearing Resistance (EN 1997-1)

As we only have a vertical load acting on the pad foundation, we only have to verify that the design bearing resistance of the sand is greater than the design load. Let’s do that. πŸ‘πŸ‘

For the final formula, we first need to calculate a lot of factors.

Shape factors (EN 1997-1 (D.1))

$$s_c = 1 + 0.2 \cdot \frac{w}{l} = 1.2$$

Inclination of loads (EN 1997-1 (D.1))

$$i_c = \frac{1}{2} \cdot (1 + \sqrt{1 – \frac{H_d}{w \cdot l \cdot c_{u.d}}}) = 1$$

Inclination of the foundation base (EN 1997-1 (D.1))

$$b_c = 1 – 2 \cdot \frac{\alpha}{\pi + 2} = 1$$

Effective vertical stresses

$$q = \gamma ‘ \cdot h’ = 4 kN/m^2$$

Design bearing resistance (EN 1997-1 (D.1))

$$\frac{R}{A} = (\pi + 2) \cdot c_{ud} \cdot b_c \cdot s_c \cdot i_c + q = 346.8 kN/m^2$$

$$R_d = 346.8 kN/m^2 \cdot w \cdot l = 1002 kN$$

Utilization

$$\eta = \frac{V_d}{R_d} = \frac{948.3 kN}{1002 kN} = 0.95$$

Therefore, the bearing capacity of the soil (clay) is verified. πŸ‘πŸ‘

πŸ‘¨β€πŸ”¬ Reinforced Concrete Design – Bending Verification

A strut and tie model is used to transfer the point load to the soil and spread the load equally along the foundation base.

Strut and tie model to distribute the point load equally to the foundation base.
Strut and tie model to distribute the point load equally to the foundation base.

Now, as concrete can’t take much tension, reinforcement will be used for the tie, and we are going to calculate how much.

The compression zone of the pad foundation creates pressure in the soil, which is visualized in the next picture.

Earth pressure $$\sigma$$ equals vertical point load $$V_d$$.

$$\sigma_s = \frac{V_d}{w \cdot l} = 328.1 kN/m^2$$

The soil pressure $\sigma_s$ creates a bending moment in the pad foundation, and we use a cantilever beam to calculate that bending moment.

Bending moment is calculated for the cantilever of the pad foundation.
Bending moment is calculated for the cantilever of the pad foundation.

The length of the cantilever is $l_c = w/2 – w_c/2 = 0.65 m$

Cantilever beam.

Now, the bending moment can be calculated.

$$M_{Ed} = \sigma_s \cdot l \cdot l_c \cdot l_c/2 = 328.1 kN/m^2 \cdot 1.7 m \cdot 0.65 m \cdot \frac{0.65 m}{2} = 117.8 kNm$$

We set the diameter of the rebars to $d_s = 10 mm$.

The lever arm of the upper layer of reinforcement is calculated as

$$d = h – c – d_s – \frac{d_s}{2} = 0.44 m$$

The required reinforcement is calculated with the following formulas. πŸ‘‡πŸ‘‡

$$\mu = \frac{M_{Ed}}{w \cdot d^2 \cdot \eta \cdot f_{c.d}} = 0.021$$

$$\omega = 1 – \sqrt{1 – 2 \cdot \mu} = 0.021$$

$$A_{s.req} = \omega \cdot \frac{w \cdot d \cdot \eta \cdot f_{c.d}}{f_{y.d}} = 597.5 mm^2$$

Check of minimum reinforcement according to EN 1992-1-1 9.2.1.1 (9.1N).

$$A_{s.min} = max(0.26 \cdot \frac{f_{ctm}}{f_{y.k}} \cdot w \cdot d; 0.0013 \cdot w \cdot d) = 961.4 mm^2$$

Because $A_{s.min} > A_s$, $A_{s.min}$ determines the reinforcement used.

Cross-sectional area of a rebar with $d_s = 10 mm$.

$$A_{s.1} = \pi \cdot (\frac{d_s}{2})^2 = 78.5 mm^2$$

Amount of rebars:

$$n = roundup(\frac{A_{s.min}}{A_{s.1}}) = 13$$

Reinforcement area:

$$A_s = n \cdot A_{s.1} = 1021 mm^2 > A_{s.min}$$

Longitudinal reinforcement of the pad foundation.
Longitudinal reinforcement of the pad foundation.

πŸ‘©β€πŸ« Reinforced Concrete Design – Shear Verification

First we check if shear reinforcement is required according to EN 1992-1-1 6.2.2.

Members not requiring design shear reinforcement

EN 1992-1-1 6.2.2 (1)

$$k = 1 + \sqrt{\frac{200}{\frac{d}{mm}}} = 1.68$$

$$\rho_1 = min(\frac{A_s}{w \cdot d}; 0.02) = 0.001$$

Design value of the shear resistance (EN 1992-1-1 (6.2.a))

$$\upsilon_{Rd.c} = max(\frac{0.18}{\gamma_c} \cdot k \cdot (100 \rho_1 \cdot f_{c.k})^{\frac{1}{3}}; \frac{0.051}{\gamma_c} \cdot k^{\frac{3}{2}} \cdot \sqrt{f_{c.k}}) = 0.38 MPa$$

$$V_{Rd.c} = \upsilon_{Rd.c} \cdot w \cdot d = 282.7 kN$$

Shear reinforcement required because $V_d > V_{Rd.c}$.

Members requiring design shear reinforcement

EN 1992-1-1 Figure 6.5

$$z = 0.9 \cdot d = 0.39m$$

Coefficient taking into account the state of the stress in the compression chord:

$$\alpha_{cw} = 1.0$$

Strength reduction factor for concrete cracked in shear (EN 1992-1-1 (6.9))

$$\upsilon_1 = 0.6$$

$$cot(\theta) = 2.5$$

$$tan(\theta) = 0.4$$

Shear resistance (EN 1992-1-1 (6.9))

$$V_{Rd.max} = \alpha_{cw} \cdot w \cdot z \cdot \upsilon_1 \cdot \frac{f_{c.d}}{cot(\theta) + tan(\theta)} = 2374 kN$$

Verification is fulfilled. πŸ‘‡πŸ‘‡

$$V_d < V_{Rd.max} = 1$$

Reduction of the design yield strength of the reinforcement (EN 1992-1-1 (6.8))

$$f_{ywd} = 0.8 \cdot f_{y.k} = 440 MPa$$

Shear links (EN 1992-1-1 (6.8))

$$A_{sw} = \frac{V_d}{z \cdot f_{ywd} \cdot cot(\theta)} = 2202 \frac{mm^2}{m}$$

Inclination of the shear reinforcement

$$\alpha = 90 deg$$

Maximum spacing (EN 1992-1-1 (9.6N))

$$s_{l.max} = 0.75 \cdot d \cdot (1 + cot(\alpha)) = 0.326 m $$

We set the spacing of the bars to s = 250 mm.

Shear reinforcement required for the whole width:

$$A_{sw} = A_{sw} \cdot w = 3744 mm^2$$

Amount of bars:

$$n = roundup(\frac{w}{s}) = 7$$

Required cross-sectional area for one stirrup:

$$A_{sw.req} = \frac{A_{sw}}{2 \cdot n} = 267.4 mm^2$$

Required bar diameter:

$$d_{s.req} = \frac{2 \cdot \sqrt{A_{sw.req}}}{\pi} = 10.4 mm$$

Therefore, a stirrup diameter of $d_{s.s} = 12 mm$ is picked.

Shear reinforcement (stirrups) in pad foundation.
Shear reinforcement (stirrups) in pad foundation.

πŸ™Œ Conclusion

Once the bearing capacity of the clay, longitudinal and shear reinforcement of the pad foundation are verified, we successfully designed the pad foundation.πŸ’―πŸ’―

If you are new to structural design, then check out more of our design tutorials where you can also learn how to design wood elements such as

But now, I would like to hear from you: Have you already designed a pad foundation in university or at your work? And which semester was that in? Tell us a bit about the structure it was supporting, as we all want to learn from each other.✍️

πŸ™‹β€β™‚οΈ Pad Foundation On Clay FAQ

What structural verifications do I have to do for a pad foundation in clay?

For only vertical loading, you have to verify the following 3 things:
– Bearing resistance of clay > Vertical design load
– Design the longitudinal reinforcement
– Design the shear reinforcement

Which standards do I use to design a pad foundation in clay?

For the geotechnical design Eurocode 7 (EN 1997-1) is used if you are in Europe. For the concrete and reinforcement design Eurocode 2 (EN 1992-1-1) applies.